Pick a wire gauge by checking four things in order: current-carrying capacity, voltage drop, ambient temperature and how many conductors share a bundle. A wire can pass one check and fail another, and the connector contact is often the real limit. This guide gives the physical data for common AWG sizes, a worked voltage-drop calculation, the temperature and bundle correction approach, and a worked example with assumed inputs. It is a sizing aid, not a substitute for the wire manufacturer's rating or the product standard that governs your application.
Updated October 3, 2026. Confirm ampacity values and connector ratings against the cited standard and the manufacturer's data for your wire and connector.
The four inputs that matter, in the order to check them:
- Continuous current (steady-state amps, not inrush).
- Allowable voltage drop at the load. Your system specification sets this; the National Electrical Code informational notes suggest keeping drop modest in building wiring, but harnesses in equipment follow the product's own limit.
- Ambient temperature along the harness route, including nearby heat sources.
- Bundle count: how many current-carrying conductors share the same loom or conduit.
Step 1: Know the Physical Data
The diameter and resistance of a solid copper conductor follow from the AWG definition. The values below are for solid copper at 20 °C, computed from the AWG formula; stranded conductors have slightly higher resistance for the same gauge because of strand lay, so use the wire manufacturer's datasheet value for the actual wire.
| AWG | Diameter (mm) | Area (mm²) | Resistance (Ω/km at 20 °C) |
|---|---|---|---|
| 30 | 0.255 | 0.051 | 338.5 |
| 26 | 0.405 | 0.129 | 133.9 |
| 24 | 0.511 | 0.205 | 84.2 |
| 22 | 0.644 | 0.326 | 53.0 |
| 20 | 0.812 | 0.518 | 33.3 |
| 18 | 1.024 | 0.823 | 20.9 |
| 16 | 1.291 | 1.309 | 13.2 |
| 14 | 1.628 | 2.081 | 8.3 |
| 12 | 2.053 | 3.309 | 5.2 |
| 10 | 2.588 | 5.261 | 3.3 |
| 8 | 3.264 | 8.366 | 2.1 |
For European drawings in mm², convert from the area column: 22 AWG is about 0.33 mm², 20 AWG about 0.52 mm², 18 AWG about 0.82 mm², 16 AWG about 1.3 mm², 14 AWG about 2.1 mm², and 12 AWG about 3.3 mm². A metric size such as 1.0 mm² or 4.0 mm² does not match an AWG size exactly, so pick the AWG size with at least the area you need. The metric conductor classes are in IEC 60228.
Step 2: Check Current Capacity from the Right Source
Ampacity depends on the insulation temperature rating, the installation and the governing standard, so there is no single table that fits every harness. Use the source that governs your product:
- Wire manufacturer's datasheet and listing (for example under UL 758 appliance wiring material or UL 1581 test methods) for the wire you actually buy.
- Industrial machinery standards such as NFPA 79 for wiring inside machine control equipment.
- The National Electrical Code ampacity table (310.16) for building wiring in raceway or cable. For copper conductors, that table gives, at the 60, 75 and 90 °C columns: 14 AWG 15, 20 and 25 A; 12 AWG 20, 25 and 30 A; 10 AWG 30, 35 and 40 A; 8 AWG 40, 50 and 55 A. These values are for building wiring and are a conservative reference, not the rating of a harness in a product, so confirm against your edition and the standard that applies.
Step 3: Calculate Voltage Drop
For a DC circuit with a return conductor of the same gauge:
Vdrop = 2 × L × R × I
L is the one-way length in meters, R is the resistance in Ω/m (the table value divided by 1,000) and I is the current in amps. The factor of 2 counts the return path.
Worked example (assumed inputs): 14 AWG carrying 15 A over a 10 ft (3.05 m) one-way run. R = 8.3 Ω/km = 0.0083 Ω/m, so Vdrop = 2 × 3.05 × 0.0083 × 15 = 0.76 V. On a 12 V supply that is about 6.3% of the voltage; on a 5 V supply it is about 15%, which most circuits cannot tolerate. For 10 AWG on the same run, R = 3.3 Ω/km gives 2 × 3.05 × 0.0033 × 15 = 0.30 V, or 6% of 5 V. Compare the drop against your own limit.
Step 4: Correct for Ambient Temperature
A conductor's allowed current falls as the surrounding temperature rises. The NEC publishes ambient-temperature correction factors in Section 310.15 (table numbering differs between editions). For copper conductors with the 60, 75 and 90 °C ratings, typical factors from that table are:
| Ambient (°C) | 60 °C wire | 75 °C wire | 90 °C wire |
|---|---|---|---|
| 40 | 0.82 | 0.88 | 0.91 |
| 50 | 0.58 | 0.75 | 0.82 |
| 60 | 0.33 | 0.58 | 0.71 |
| 70 | — | 0.33 | 0.58 |
| 80 | — | — | 0.41 |
Check the factors against the edition you use. For wire sold under a manufacturer rating, use the manufacturer's own temperature curve if it publishes one.
Step 5: Correct for Bundle Size
When many current-carrying conductors share a bundle, they heat each other. The NEC adjustment factors for more than three current-carrying conductors in a raceway or cable are 80% for 4 to 6, 70% for 7 to 9, 50% for 10 to 20, 45% for 21 to 30, 40% for 31 to 40, and 35% for 41 or more. Count only conductors that carry current during normal operation; a grounding conductor that does not normally carry current is not counted. These factors are written for building wiring, so for a harness in a product, ask the wire manufacturer or the governing product standard whether they apply or whether they publish their own.
Worked Example with Assumed Inputs
Assume a harness with 90 °C rated 14 AWG copper wire, a 60 °C ambient, six current-carrying conductors in the bundle, and a load of 12 A per conductor. Starting from the NEC building-wiring value of 25 A at 90 °C: 25 A × 0.71 (temperature) × 0.80 (4 to 6 conductors) = 14.2 A. A 12 A load is under 14.2 A, so 14 AWG passes this ampacity check with a 2.2 A margin. At 12 A the margin is thin, so check the voltage drop for your length and the contact rating of the connector before you accept it. These numbers illustrate the method; replace them with your wire's rating and your own conditions.
Check the Connector Contact, Not Only the Wire
The wire is rarely the only limit on a real harness. Every contact has its own rated current for specific wire sizes, plating and temperature, stated in the connector manufacturer's datasheet. Compare the contact rating with the current and the wire size on the drawing. If the contact rates lower than the wire, the contact is the constraint: either choose a larger contact or reduce the load. Do not assume a wire's ampacity carries over to the terminal.
Practical Drawing Call-Outs
- Size the shared return for the sum. If one return carries current from several loads, size it for the total current, not for one load.
- Do not round up blindly. A larger gauge costs more copper and may not fit the contact; step up only as far as the checks require.
- Document the assumptions. State the ambient temperature, bundle count and insulation rating the sizing is based on, on the drawing or in the design note, so the supplier builds to the same case.
FAQ
Which standard should I follow for a harness inside equipment?
The one that governs your product: the wire manufacturer's listing, an industrial machinery standard such as NFPA 79, or your customer's specification. The NEC is a building-wiring code. It is a useful reference for correction methods, not a substitute for the product standard.
What about flex life and high-flex wire?
Ampacity and flex life are separate checks. A high-flex wire is built with finer strands for repeated bending; the manufacturer states its flex rating and its current rating separately. See the strain relief and routing guide for bend-radius considerations.
How does this change above 600 V?
High-voltage harnesses add insulation-rating and creepage requirements that depend on the system and its standard. Use the standard for your application and the wire manufacturer's voltage rating, and do not extend a low-voltage sizing method to a high-voltage design.
Next Step
Put the current, length, ambient temperature, bundle count and insulation rating on the drawing, and send it through the RFQ page so the gauge can be reviewed with the connector ratings. See also the DFM checklist and the crimping capability page.
Sources
- NFPA 70, National Electrical Code, Sections 310.15 and 310.16 (confirm table numbering in your edition).
- UL 758 and UL 1581 for appliance wiring material and wire test methods; NFPA 79 for industrial machinery electrical equipment.
- IEC 60228 for conductor classes and metric sizes.
- Wire manufacturers' datasheets for the wire you select.



